A adaptive Method to intelligently detect the inconsistency in topological calibration from Power Grid GIS data

IP.com Disclosure Number: IPCOM000234899D
Publication Date: 2014-Feb-13
Document File: 7 page(s) / 126K

Publishing Venue

The IP.com Prior Art Database

Abstract

A adaptive Method has been proposed which could intelligently detect the inconsistency in topological calibration from Power Grid GIS(Geographic Information System) data. Firstly, Automatically Check the topology data problem by introducing extra infomation and using electrical characters. In this step we check the topology with static electrical characters as well as dynamic electrical characters combined with load data from SCADA(Supervisory Control And Data Acquisition) system and equipment information from asset management system in power grid. Secondly, advanced data mining analysis method has been exploited by modeling extra information from power distribution fault outage. In this step, Support Confidence and Conviction is calculated for each item set which is extracted from power distribution repair system and then decide whether update GIS topology information according to association analysis data and current GIS topology data.

This text was extracted from a PDF file.
This is the abbreviated version, containing approximately 54% of the total text.

Page 01 of 7

A adaptive Method to intelligently detect the inconsistency in topological calibration from Power Grid GIS data

Background Knowledge:

GIS Application and Topology Data in Power Grid

-GIS (Geographic Information System ): A Basic System in the Power Grid Company

-More and more important, widely used in electric power company.
-GIS provides the Topology data which is the basic import of topology analysis
-Topology analysis is the basis of a lot of applications, such as grid planning, outage range analysis, outage task display, power source tracking, etc.


Importance of checking the quality of Topology Data

-Wrong Data, Wrong Decision
-Both important for the IT vendor and electrical power company

Diagram for Topology Connection Problem

1


Page 02 of 7

Disadvantage of Traditional Method

Traditional Method in checking topology data
-Manually Self-checked by the data owner
-Manually checked when the bad connection causes an unreasonable result


Difficulty in checking topology connection problem
-Massive GIS data: More than 1.2 Million records in a city-level power company
-Different Owner: Collected from different departments
-Very time-consuming if manually checking the data: 20 persons, 3 months maintenance, 5 months/4 rounds checking

Difficult to check the wrong connection problem
-No good technical approaches and tools till now

Our methods:
Automatically Check the topology data problem


Introduce Extra Infomation and use electrical characters in power grid
-Combination with load data from SCADA(Supervisory Control And Data Acquisition) system and equipment information from asset management system
-Check with static electrical characters


Transformer Current Limitation Rule


Transformer Capacity Limitation Rule


Switch Current Limitation Rule

-Check with dynamic electrical characters
principles / rules in power grid, such as P=UI, U=IR, E=∫Pdtand Kirchoff's law

Introduce Extra Infomation from power distribution fault outage and use Data Mining analysis method .
-Extract infomation...